Masterpact™ NT and NW Universal Power Circuit Breakers
Masterpact™ Circuit Breakers
13
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Ratings
Table 1: Ratings for ANSI C37 Certified Masterpact NW Circuit Breakers
Frame Rating 800/1600 A 2000 A 3200/4000 A
1
1
4000 A standard width circuit breaker is not available in L1 interrupting rating code or drawout construction.
4000/5000/6000 A
2
2
ArcBlok circuit breakers are available only to 5000 A.
Interrupting Rating Code N1 H1 H2 H3 L1
3,
4
3
Interrupting ratings (kAIR) at 50 Hz: 200 kA (254 Vac), 150 kA (508 Vac), 100 kA (635 Vac).
4
The interrupting ratings L1 and L1F are available only in 3P, drawout construction.
L1F
4
H1 H2 H3 L1
3, 4
L1F
4
H1 H2 H3 L1
3, 4
H2 H3 L1
3, 4
Interrupting Current (kAIR)
254 Vac 50/60 Hz
508 Vac 50/60 Hz
635 Vac 50/60 Hz
42
42
42
65
65
65
85
85
85
100
100
85
200
200
130
200
200
130
65
65
65
85
85
85
100
100
85
200
200
130
200
200
130
65
65
65
85
85
85
100
100
85
200
200
130
85
85
85
100
100
85
200
200
130
Short-Time Withstand Current
(kA)
Vac 50/60 Hz,
0.5 s
42 65 85 85 30 22 65 85 85 30 22 65 85 85 100 85 85 100
Built In Instantaneous Override
(Peak kA ±10%)
5
5
55 kA for 800 A circuit breaker frame with 100 A or 250 A sensor.
5
5
190 80
5
55 190 80 55 190 270 270
Close and Latch Ratings
(Peak kA)
Vac 50/60 Hz 90 150 90 90 55 50 150 90 90 55 50 150 90 90 90 170 170 90
Tested to show arc flash hazard risk
category as referenced by NFPA70E
Yes———— Yes————
Breaking Time 25 to 30 ms (with no intentional delay) 9 ms for L1 and L1F
Closing Time 70 ms
Sensor Rating
100–800 A
800–1600 A
1000–2000 A 1600–4000 A
2000–4000 A
2500–5000 A
3000–6000 A
Endurance Rating (C/O
Cycles)
(with no maintenance)
Mechanical 12,500 10,000 10,000 5000 5000
Electrical 2800 1000 1000 1000 1000
Table 2: Ratings for ANSI C37 Certified Masterpact NW Non-Automatic Switches
Frame Rating 800 A 1600 A 2000 A 3200 A 4000 A 5000 A
Withstand Rating Code HA HA HA HA HA HA
Breaking Capacity with
External Relay (kA),
50/60 Hz
254 Vac 65 65 65 65 85 85
508 Vac 65 65 65 65 85 85
635 Vac 65 65 65 65 85 85
Short-Time Withstand Current
(kA) Vac 50/60 Hz, 0.5 s
65 65 65 65 85 85
Table 3: Ratings for ANSI C37 Certified Masterpact NW Automatic Switches
Frame Rating 800 A 1600 A 2000 A 3200 A 4000 A
1
1
4000 A standard width automatic switch is not available in HC withstand rating code or drawout construction.
5000 A
Withstand Rating Code HF HC HF HC HF HC HF HC HF HC HF HC
Breaking Capacity with
External Relay (kA),
50/60 Hz
254 Vac 100 200 100 200 100 200 100 200 100 200 100 200
508 Vac 100 200 100 200 100 200 100 200 100 200 100 200
635 Vac 85 130 85 130 85 130 85 130 85 130 85 130
Short-Time Withstand Current (kA)
50/60 Hz, 1.5 s
85 30 85 30 85 30 85 100 85 100 85 100