Universal Remote Control MX-880Z - SPECS SHEET Technical Information Seite 21

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 180
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 20
Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
21
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Power Supply Information
Ammeter (A) Trip Unit Without 24 Vdc Power Supply at F1 and F2
Provides fault protection for LSIG functions
Provides LED trip indication (powered by an onboard battery)
All display functions and trip unit features power-up with current flow on one phase greater than or
equal to the values in the table to the left
Ground-fault push-to-trip button works for testing ground fault with current flow on one phase
greater than or equal to the values shown in the following table
Ammeter (A) Trip Unit With 24 Vdc Power Supply at F1 and F2
The Ammeter (A) trip unit provides all of the above plus additional functionality when powered by
external 24 Vdc power supply:
Ammeter and bar graph displays are functional with or without current flowing through the circuit
breaker
Trip settings and (Max) current readings can be accessed on the display by pressing navigation
button with or without current flowing through the circuit breaker
Ground-fault push-to-trip button works for testing ground fault with or without current flowing
through the circuit breaker
Optional Modbus™ communications—Also requires a separate 24 Vdc power supply for the circuit
breaker communications module
NOTE: Ground-fault push-to-trip button will also be functional if a hand-held test kit or full-function test
kit is powering the trip unit.
Power (P) and Harmonic (H) Trip Unit Without 24 Vdc Power Supply at F1 and F2
The P and H trip units were designed to be used with the external 24 Vdc power supply. The large LCD
display requires too much current to be powered by current flow through the circuit breaker. The P and
H trip units do have a voltage power supply which will power the trip unit with 100 Vac or more between
two phases or phase to neutral. The standard configuration for the voltage probes inside the circuit
breaker is at the bottom connections. If the circuit breaker was open in a top fed application, there
would be no voltage at the bottom of the circuit breaker and the trip unit would not be powered.
Provides fault protection for LSIG functions
Provides LED trip indication (powered by an onboard battery)
NOTE: Ground-fault push-to-trip button works for testing ground fault if the trip unit is powered by the
voltage power supply. The ground-fault push-to-trip is also functional if a hand-held test kit or full-
function test kit is powering the trip unit.
Power (P) and Harmonic (H) Trip Unit With 24 Vdc Power Supply at F1 and F2
Provides all of the above
LCD display and backlight are functional
Ground-fault push-to-trip button works for testing ground fault
All metering, monitoring, and history logs are functional
Communications from trip unit to M2C and M6C programmable contact modules are powered by a
24 Vdc supply at F1 and F2. M6C also requires a 24 Vdc external power supply
Modbus communications—Also requires a separate 24 Vdc power supply for the circuit breaker
communications module.
NOTE: Ground-fault push-to-trip button will also be functional if hand-held test kit or full-function test kit
is powering the trip unit.
Sensor Plug
Value (In)
Minimum
Ground-
Fault
Pickup
100–250 A
30% of
sensor
rating
400–1200 A
20% of
sensor
rating
1600–6300 A 500 A
Seitenansicht 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 179 180

Kommentare zu diesen Handbüchern

Keine Kommentare