Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
32
05/2014
Waveforms may be displayed on the graphic screen of Micrologic H trip units or communicated over a
networked system. The recording takes place over one cycle with a measurement range of 0 to 1.5 I
N
for current and 0 to 690 volts for voltage. The resolution is 64 points per cycle.
Customized Alarm Programming
The instantaneous value of each measurement can be compared to user-set high and low thresholds.
Overrun of a threshold generates an alarm. Programmable action can be linked to each alarm, including
circuit breaker opening, activation of an M2C or M6C contact, recording of measurements in a log, etc.
Event Logs
Each event is recorded with:
The date, time, and name of the event.
The event characteristics.
Additional Technical Characteristics for Type P and Type H Trip Units
Setting the display language: System messages can be displayed in six different languages:
English - US
English - UK
French
—German
Spanish
Italian
The desired language is selected via the keypad.
Protection functions: All current-based protection functions require no auxiliary source. Voltage-
based protection functions are connected to AC power via a voltage measurement input built into
the circuit breaker on the bottom side. (Optional external voltage measurement is available.)
Accuracy of measurements (including sensors):
Voltage (V) 1%
Current (A) 1.5% (higher accuracy [1%] may be achieved with special calibration on the current
transformer [CT characterization option])
Frequency (Hz) 0.1 Hz
Power (W) and energy (Wh) 2.5%
The Micrologic H trip unit uses a dedicated metering data chain separate from the protection
data chain so that a greater number of data samples can be used for metering. This increases
the number of samples taken per time period, which in turn gives the H trip unit a higher degree
of metering accuracy.
Stored information: The fine setting adjustments, the last 100 events and the maintenance record
remain in the trip unit memory even when power is lost.
Reset: An individual reset, via the keypad or remotely, will reset alarms, minimum and maximum
data, peak values, counters and the indicators.